China FN7-12 Series Indoor High Voltage Load Switch and Fuse Combination - Reliable Suppliers & Factory
Technical Specification
Rated voltage (KV) |
12 |
||
Insulation level |
1min frequency voltage (KV) |
Phase to phase, to earth 42 |
Isolation fracture 48 |
Lightning impulse withstand voltage (KV) |
Phase to phase, to earth 75 |
Isolation fracture 85 |
|
Rated current (A) |
400 |
630 |
|
4S Rated thermal current (KA) |
12.5 |
20 |
|
Rated active load breaking current (KA Peak) |
31.5 |
50 |
|
Rated short circuit making current (KA peak) |
31.5 |
50 |
|
Item |
Model |
DS |
DX |
L |
R |
RA |
F |
Use |
|
Grounding switch incoming feeder side |
Grounding switch outgoing feeder side |
Interlock device |
Fuse |
Impact fuse |
Electric sub-gate devices |
||||
Load Switches |
Non-impact fuse |
FN7-12 |
- |
- |
- |
- |
- |
- |
Line load switch |
FN7-12DSL |
△ |
- |
△ |
- |
- |
- |
|||
FN7-12DXL |
- |
△ |
△ |
|
|
|
|||
FN7-12R |
- |
- |
- |
△ |
- |
- |
Transformer Protection |
||
FN7-12DSLR |
△ |
- |
△ |
△ |
- |
- |
|||
FN7-12DXLR |
- |
△ |
△ |
△ |
- |
- |
|||
With impact fuse |
FN7-12RAF |
- |
- |
- |
- |
△ |
△ |
||
FN7-12DSLRAF |
△ |
- |
△ |
- |
△ |
△ |
|||
FN7-12DXLRAF |
- |
△ |
△ |
- |
△ |
△ |
|||
Dimension
Frequently Asked Questions
Q
What is the rated voltage of the FN7-12 load switch?
The FN7-12 series load switch has a rated voltage of 12 KV, making it suitable for medium-voltage distribution networks operating within this voltage class.
Q
What rated current options are available for the FN7-12 load switch?
The FN7-12 load switch is available in two rated current options: 400 A and 630 A, allowing selection based on the specific load requirements of your application.
Q
What is the lightning impulse withstand voltage of the FN7-12 series?
The lightning impulse withstand voltage is 75 KV for phase-to-phase and phase-to-earth, and 85 KV across the isolation fracture, ensuring reliable protection against transient overvoltages.
Q
What is the difference between FN7-12 models with and without impact fuse?
Models without impact fuse (e.g., FN7-12, FN7-12DSL, FN7-12R) are typically used for line load switching or basic transformer protection. Models with impact fuse (e.g., FN7-12RAF, FN7-12DSLRAF) incorporate an impact fuse and electric sub-gate device, providing enhanced transformer protection by automatically tripping the switch upon fuse operation.
Q
What do the DS and DX suffixes indicate in the FN7-12 model nomenclature?
The suffix DS indicates that the model is equipped with a grounding switch on the incoming feeder side, while DX indicates a grounding switch on the outgoing feeder side. These configurations provide safe earthing options for maintenance and operational safety.
Q
What are the main application scenarios for the FN7-12 load switch series?
The FN7-12 series is designed for two primary application scenarios: line load switching (suitable for ring main units and feeder automation) and transformer protection (used in combination with fuses to safeguard distribution transformers from overloads and short-circuit faults).