China GN30-12 Series Indoor HV Rotary Disconnect Switch Suppliers and Factory for 10kV Power Systems
Technical Specification
| Item | GN30-12/400-12.5 | GN30-12/630-20 | GN30-12/1000-31.5 | GN30-12/1250-31.5 | |
| GN30-12D/400-12.5 | GN30-12D/630-20 | GN30-12D/1000-31.5 | GN30-12D/1250-31.5 | ||
| Rated Voltage (KV) | 12 | ||||
| Rated Current (A) | 400 | 630 | 1000 | 1250 | |
| Rated Short-time Withstand Current (KA) | 12.5 | 20 | 31.5 | ||
| Rated Short-circuit Duration (S) | 4 | ||||
| Rated Peak Withstand Current (KA) | 31.5 | 50 | 80 | ||
| Rated Insulating Level | Lightning Impulse Withstand Voltage (KV) | Phase to phase / to earth: 75 | Across open contacts: 85 | |||
| 1 min. PF Withstand Voltage (KV) | Phase to phase / to earth: 42 | Across open contacts: 48 | ||||
Product Model
Dimension
| GN30-12 | GN30-12D/1250 | |||||||||||||
| 400A 630A | 1000A | 1250A | 400A 630A | 1000A | 1250A | |||||||||
| A | C | A | C | A | C | A | B | C | A | B | C | A | B | C |
| ~560 | ~315 | ~580 | ~332 | ~580 | ~295 | ~550 | ~610 | ~240 | ~575 | ~615 | ~245 | ~580 | ~600 | ~295 |
Frequently Asked Questions
Q
What is the rated voltage of the GN30-12 series indoor high-voltage disconnect switch?
The GN30-12 series is designed for a rated voltage of 12 KV, making it suitable for indoor medium-voltage power distribution systems.
Q
What rated current options are available for the GN30-12 series?
The GN30-12 series is available in four rated current options: 400A, 630A, 1000A, and 1250A, covering a wide range of power distribution requirements.
Q
What is the difference between the GN30-12 and GN30-12D models?
The GN30-12D is a variant of the standard GN30-12 model. Both share the same rated voltage, current, and short-circuit withstand parameters, but differ in their dimensional configuration (notably the B-dimension), making the GN30-12D suitable for different installation space requirements.
Q
What is the rated short-time withstand current and duration for the GN30-12/1000-31.5?
The GN30-12/1000-31.5 has a rated short-time withstand current of 31.5 KA with a rated short-circuit duration of 4 seconds, and a corresponding rated peak withstand current of 80 KA.
Q
What are the insulation withstand voltage levels for the GN30-12 series?
For lightning impulse withstand voltage, the phase-to-phase and phase-to-earth level is 75 KV, and across open contacts is 85 KV. For 1-minute power frequency withstand voltage, the phase-to-phase and phase-to-earth level is 42 KV, and across open contacts is 48 KV.
Q
How should I select the correct GN30-12 model based on installation dimensions?
Refer to the dimension table and drawing provided above. Key dimensions (A, B, C) vary by current rating and model variant (GN30-12 or GN30-12D). For example, the GN30-12/400A–630A has dimensions A≈560mm and C≈315mm, while the GN30-12D/1250A has A≈580mm, B≈600mm, and C≈295mm. Always verify available cabinet space before selection.