📋 Technical Specification
Item |
GN30-12M/400-12.5 |
GN30-12M/630-20 |
GN30-12M/1000-31.5 |
GN30-12M/1250-31.5 |
|
GN30-12DM/400-12.5 |
GN30-12DM/630-20 |
GN30-12DM/1000-31.5 |
GN30-12DM/1250-31.5 |
||
Rated Voltage (KV) |
12 |
||||
Rated Current (A) |
400 |
630 |
1000 |
1250 |
|
Rated Short-time Withstand Current (KA) |
12.5 |
20 |
31.5 |
||
Rated Short-circuit Duration (S) |
4 |
||||
Rated Peak Withstand Current (KA) |
31.5 |
50 |
80 |
||
Rated Insulating Level |
Lightning Impulse Withstand Voltage (KV) |
Phase to phase / to earth: 75 | Across open contacts: 85 |
|||
1 min. PF Withstand Voltage (KV) |
Phase to phase / to earth: 42 | Across open contacts: 48 |
||||
🔖 Product Model
📐 Dimension
❓ Frequently Asked Questions
Q
What is the rated voltage of the GN30-12 series disconnector?
A
The GN30-12 series disconnector has a rated voltage of 12 KV, making it suitable for medium-voltage switchgear applications.
Q
What rated current options are available for the GN30-12 series?
A
The GN30-12 series is available in four rated current options: 400A, 630A, 1000A, and 1250A, covering a wide range of load requirements.
Q
What is the difference between the GN30-12M and GN30-12DM models?
A
The GN30-12M and GN30-12DM share the same electrical specifications. The "DM" designation typically indicates a double-pole or specific mounting/drive configuration. Please refer to the product model diagram for detailed structural differences.
Q
What is the rated short-time withstand current for the 1000A and 1250A versions?
A
Both the 1000A and 1250A versions share a rated short-time withstand current of 31.5 KA, with a corresponding rated peak withstand current of 80 KA and a short-circuit duration of 4 seconds.
Q
What are the insulation withstand voltage levels for the GN30-12 series?
A
The lightning impulse withstand voltage is 75 KV phase-to-phase/to earth and 85 KV across open contacts. The 1-minute power frequency withstand voltage is 42 KV phase-to-phase/to earth and 48 KV across open contacts.
Q
Where can I find the dimensional drawings for the GN30-12 disconnector?
A
The dimensional drawings for the GN30-12 series are provided in the "Dimension" section above. The diagrams illustrate the installation dimensions and structural layout for accurate engineering and installation planning.