China HXGN17-12 Box-Type Fixed Metal Enclosed Switchgear Suppliers - Reliable High-Voltage Solutions from Factory
Product Model
Technical Parameters
| No. | Item | Unit | FN12-12 | FZN25-12 | |
|---|---|---|---|---|---|
1 |
Rated Voltage |
KV |
12 |
||
2 |
1min Power Frequency Withstand Voltage |
Phase-to-ground and inter-phase 42; Isolation gap 48 |
|||
3 |
Lightning Impulse Voltage (Peak) |
Phase-to-ground and inter-phase 75; Isolation gap 85 |
|||
4 |
Rated Frequency |
Hz |
50 |
||
5 |
Load Switch |
Rated Current |
A |
630 |
|
6 |
Service Life under Rated Current |
Times |
Not less than 100 |
||
7 |
Breaking No-load Transformer Capacity |
kV/A |
1250 |
1600 |
|
8 |
Rated Thermal Stable Current |
kA/s |
20/4; Grounding Switch 20/2 |
||
9 |
Rated Dynamic Stable Current (Peak) |
kA |
50 |
||
10 |
Rated Short-circuit Making Current (Peak) |
50 |
|||
11 |
Fuse Rated Current |
A |
125 |
||
12 |
Combined Apparatus |
Rated Transfer Current |
A |
1200 |
2000 |
13 |
Rated Short-circuit Breaking Current |
kA |
31.5 |
||
14 |
Matching Fuse Model |
S□LAJ-12 |
|||
15 |
Mechanical Life |
Times |
2000 |
10000 |
|
16 |
1min Power Frequency Withstand Voltage for Auxiliary Circuit |
kV |
2 |
||
17 |
Operating Voltage of Operating Mechanism |
V |
AC/DC 220; 110 |
||
18 |
Protection Level |
IP2X |
|||
19 |
Dimensions |
600(700)×900×2000(1800) |
|||