China ZN63(VS1)-24 Indoor High Voltage Vacuum Circuit Breaker - Reliable Suppliers and Factory Solutions for Power Distribution
Technical Specification
NO. |
Item |
Units |
Parameters |
||
1 |
Rated voltage |
kV |
24 |
||
2 |
Rated frequency |
Hz |
50 |
||
3 |
Rated current |
A |
630 |
1250 |
1600 |
4 |
Rated short-circuit breaking current |
kA |
20 |
25 |
31.5 |
5 |
Rated short-circuit closing current (peak) |
kA |
50 |
63 |
80 |
6 |
Rated short-circuit duration |
S |
4 |
||
7 |
Rated short-circuit breaking current breaking times |
Times |
20 |
||
8 |
Rated operating sequence |
|
O-0.3s-CO-180s-CO |
||
9 |
Rated lightning impulse withstand voltage (fracture) |
kV |
125 |
||
|
1 min power frequency withstand voltage (fracture) |
kV |
65 |
||
10 |
Closing time |
ms |
≤100 |
||
11 |
Opening time |
ms |
≤50 |
||
12 |
Mechanical life |
Times |
20000 |
||
13 |
Rated storage and operation voltage |
V |
~220/110 (AC/DC 220/110) |
||
14 |
Breaking life |
ms |
≤65 |
||
15 |
Energy storage time |
s |
≤10 |
||
Product Model
Dimension
Frequently Asked Questions
Q
What is the rated voltage of this vacuum circuit breaker?
The rated voltage of this vacuum circuit breaker is 24 kV, making it suitable for medium-voltage power distribution systems operating at this voltage level.
Q
What rated current options are available for this circuit breaker?
This circuit breaker is available in three rated current options: 630 A, 1250 A, and 1600 A, allowing flexible selection based on the specific load requirements of your application.
Q
What is the mechanical life expectancy of this vacuum circuit breaker?
The mechanical life of this vacuum circuit breaker is 20,000 operations, ensuring long-term reliability and reduced maintenance costs over the product's service life.
Q
What are the closing and opening times of this circuit breaker?
The closing time is ≤100 ms and the opening time is ≤50 ms. These fast response times ensure effective protection of electrical equipment during fault conditions.
Q
What control voltage does this vacuum circuit breaker support?
The rated storage and operation voltage supports AC/DC 220 V and 110 V, providing compatibility with a wide range of substation control power supply systems.
Q
What is the rated short-circuit breaking current and how many breaking operations are supported?
The rated short-circuit breaking current ranges from 20 kA to 31.5 kA depending on the selected model. The breaker supports up to 20 rated short-circuit breaking operations, ensuring robust performance under fault conditions.