China ZW10-12XDG Series 12kV Dual Power Switch Device - Reliable Suppliers & Factory for High Voltage Solutions
No. |
Item |
Units |
Parameters |
|
1 |
Rated voltage |
kV |
12 |
|
2 |
Max. operating voltage |
kV |
12 |
|
3 |
Rated current |
A |
630 |
|
4 |
Rated short-circuit load breaking current |
kA |
20 |
|
5 |
Rated short-circuit closing current (peak) |
kA |
50 |
|
6 |
Rated peak withstand current |
kA |
50 |
|
7 |
Rated short-time 1min. withstand current |
kA |
20 |
|
8 |
Rated insulation level |
1min PF withstand voltage (Dry type) |
kV |
42 |
Lightning impulse withstand voltage (peak) |
75 |
|||
9 |
Rated operating sequence |
|
O-0.3s-CO-180s-CO |
|
10 |
Mechanical life |
Times |
10000 |
|
11 |
Off/On times of rated short-circuit breaking current |
Times |
30 |
|
12 |
Operator mechanism rated closing voltage |
V |
220 |
|
13 |
Operator mechanism rated opening voltage |
V |
220 |
|
14 |
Clearance between open contacts |
mm |
9±1 |
|
15 |
Over-travel |
mm |
3±0.5 |
|
16 |
Three phase opening, closing not synchronism |
ms |
≤2 |
|
17 |
Contact closing bounce time |
ms |
≤2 |
|
18 |
Average opening speed |
m/s |
1.0+0.2 |
|
19 |
Average closing speed |
m/s |
0.7±0.15 |
|
20 |
Closing time |
Max. operating voltage |
s |
0.015–0.05 |
Min. operating voltage |
0.03–0.06 |
|||
21 |
Closing time |
s |
0.025–0.05 |
|
22 |
The main loop resistance for each phase |
uΩ |
≤180 |
|
23 |
Dynamic and static contact erosion limit |
mm |
3 |
|