| Item | Units | Parameters | ||
| Rated voltage | KV | 12 | ||
| Rated insulation level | 1min power frequency withstand voltage | Dry | KV | To earth, phase to phase 48 Fracture 48 |
| Wet | 34 | |||
| Lightning impulse withstand voltage (peak) | To earth, phase to phase 85 Fracture 85 | |||
| Rated frequency | Hz | 50 | ||
| Rated current | A | 630 | ||
| Rated short-circuit breaking current | KA | 12.5/16/20 | ||
| Rated short-circuit closed current(peak) | KA | 50 | ||
| Rated peak withstand current | KA | 50 | ||
| Rated short-time withstand current(4s) | KA | 20 | ||
| Rated operating sequence | O-0.3s-CO-180s-CO | |||
| Switch on/opening time | ms | 25-50/15-50 | ||
| Rated short-circuit breaking current breaking times | Times | 30 | ||
| Mechanism life | Times | 10000 | ||
| The control circuit and auxillary circuit 1 min power frequency withstand voltage | v | 2000 | ||
| Rated operating voitage and auxiliary circuit rated voltage | v | DC220/AC220 | ||
| Over-current tripper | Rated current | a | 5 | |
| Tripping current precision | % | ±10 | ||
Product Model
Dimension
Frequently Asked Questions
What is the rated voltage of this equipment?
The equipment is designed for a rated voltage of 12KV, making it suitable for medium-voltage power distribution systems.
What is the mechanical lifespan of the mechanism?
The mechanism is built for high durability with a rated life of up to 10,000 operations under standard conditions.
Does the control circuit support both AC and DC power?
Yes, the rated operating voltage for the auxiliary and control circuits is compatible with both DC220V and AC220V.
What is the lightning impulse withstand voltage?
The unit provides robust protection with a peak lightning impulse withstand voltage of 85KV (to earth and phase to phase).
What are the options for rated short-circuit breaking current?
The product is available in three configurations for short-circuit breaking current: 12.5KA, 16KA, and 20KA.
What is the rated short-time withstand current duration?
The device can withstand a rated short-time current of 20KA for a duration of 4 seconds.