Leave Your Message
pro_banner_013
China ZW32-24 Series Outdoor High Voltage Vacuum Circuit Breaker - Reliable Suppliers & Factory for 24kV Solutions

China ZW32-24 Series Outdoor High Voltage Vacuum Circuit Breaker - Reliable Suppliers & Factory for 24kV Solutions

The ZW32-24 Series is a state-of-the-art outdoor high voltage vacuum circuit breaker designed for 24kV, 50Hz three-phase systems. Perfect for applications in urban networks, rural electrification, mining, and railways, this circuit breaker ensures reliable switching of various load currents in frequently operated environments. Manufactured in China, our circuit breaker features a durable stainless steel shell with anti-corrosion treatment, silicone rubber insulated columns, and a spring mechanism, emphasizing miniaturization and maintenance-free operation. With intelligent capabilities and an environmentally friendly design that generates zero pollution, it meets the strict standards of GB1984-2003, DL/T402-2007, and DL/T403-2000. As a leading supplier and factory, we are committed to providing high-quality solutions for your electrical needs

    Technical Specification


    No.

    Item

    Units

    Parameters

    1

    Rated voltage

    kV

    24

    2

    Rated frequency

    Hz

    50

    3

    Rated current

    A

    630

    1250

    4

    Rated short-circuit breaking current

    kA

    20

    25

    5

    Rated peak withstand current (peak)

    KA

    50

    63

    6

    Rated short-circuit closing current (peak)

    kA

    50

    63

    7

    Rated short-time withstand current and duration

    kA/s

    20/4

    25/4

    8

    Rated operation sequence

     

    O-0.3s-CO-180s-CO

    9

    Mechanical life

    Times

    10000

    10

    Breaking times of rated short-circuit breaking current

    Times

    20

    11

    1min power frequency withstand voltage

    (wet) over the ground / interphase / fracture

    kV

    50/65

    (dry) over the ground / interphase / fracture

    65/79

    Secondary loop

    2

    12

    Lighting impulse withstand voltage (peak) Over the ground, interphase / fracture

    kA

    125/145

    13

    Weight

    kg

    115

    Product Model


    Product Model Diagram

    Dimension


    Dimension Drawing

    Frequently Asked Questions


    • Q1 What is the rated voltage of this circuit breaker?
      The rated voltage of this circuit breaker is 24 kV, making it suitable for medium-voltage power distribution systems operating at that level.
    • Q2 What rated current options are available?
      This circuit breaker is available in two rated current options: 630 A and 1250 A, allowing it to be selected according to the specific load requirements of your installation.
    • Q3 What is the rated short-circuit breaking current?
      The rated short-circuit breaking current is 20 kA for the standard version and 25 kA for the enhanced version, ensuring reliable fault interruption under high-fault current conditions.
    • Q4 How many mechanical operations can this circuit breaker perform?
      The circuit breaker has a mechanical life of 10,000 operations, demonstrating excellent durability and reliability for long-term use in power distribution applications.
    • Q5 What is the rated operation sequence of this product?
      The rated operation sequence is O-0.3s-CO-180s-CO, which defines the standard opening and closing cycle the breaker can perform without exceeding its thermal and mechanical limits.
    • Q6 What is the lightning impulse withstand voltage of this circuit breaker?
      The lightning impulse withstand voltage (peak) is 125 kA over the ground and interphase, and 145 kA across the fracture, ensuring robust protection against transient overvoltages and lightning strikes.