China ZW43-12(G)/630-20 Outdoor High-Voltage Vacuum Circuit Breaker - Reliable Suppliers & Factory Options
Technical Specification
No. |
Item |
Units |
Parameters |
||
1 |
Rated voltage |
kV |
12 |
||
2 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test (on the ground, white, fracture) |
42/48 |
|
Wet test |
34 |
||||
Lightning impulse withstand voltage (peak, white / fracture) |
75/85 |
||||
3 |
Rated current |
A |
630 |
||
4 |
Rated short circuit breaking current |
kA |
20 |
||
5 |
Rated operating sequence |
|
O~0.3-CO-180S-COS |
||
6 |
Rated short-circuit breaking current breaking times |
Times |
30 |
||
7 |
Rated short-circuit current (peak) |
kA |
50 |
||
8 |
Rated peak withstand current |
||||
9 |
Rated short time withstand current |
20 |
|||
10 |
Rated short duration |
S |
4 |
||
11 |
Sub explain time |
0.040~0.060 |
|||
12 |
Closing time |
0.070~0.120 |
|||
13 |
Mechanical life A |
Times |
10 |
||
14 |
Rated operating voltage closing |
V |
AC/DC 220/110 |
||
15 |
Rated voltage switching operation |
AC/DC 220/110 |
|||
16 |
Overcurrent protection |
Current setting multiples |
|
0.2~2.5 |
|
Setting current tolerance |
|
±10% |
|||
Delay setting value |
S |
0~5 |
|||
Delay tolerance |
|
±10% |
|||
17 |
Interruption Protection |
Current setting multiples |
|
2.5-10 |
|
Setting current tolerance |
|
±10% |
|||
Delay setting value |
S |
0-0.5 |
|||
Delay tolerance |
|
±10% |
|||
18 |
AC charging auxiliary control unit into the current |
RATINGS |
A |
5 |
|
Fluctuation range |
A |
0.5~8 |
|||
Product Model