Leave Your Message

FZN/FZRN25-12DG/125-31.5 Indoor high voltage vacuum load isolation switch

The FZN/FZRN25-12DG Series is a high voltage vacuum load isolation switch for 12kV, 50Hz systems. It uses a vacuum interrupter with separate fractures for strong insulation, handling 42kV power frequency and 75kV lightning impulse. Rated at 25kA short-time current and over 10,000 operations, it offers reliable switching and isolation for industrial and ring network applications.

    Technical specification

    No.

    Item

    Units

    Vacuum load isolation switch

    Vacuum load isolation switch - fuse combinations FZN25-12DG/T200-31.5

    FZN25-12DG/T630-25

    FZN25-12DG/T1250-25

    1

    Rated voltage

    kV

    12

    2

    Rated frequency

    Hz

    50

    3

    Rated current

    A

    630

    1250

    200

    4

    Rated short time withstand current

    kA

    25

    5

    Rated peak withstand current

    kA

    63

    6

    Rated short-circuit current

    KA

    63

    80

    7

    Rated active load breaking current

    A

    1250

    1250

    8

    Rated closed loop breaking current

    A

    1250

    1250

    9

    Breaking load transformer

    kVA

    2000

    10

    Ground fault current

    A

    20

    11

    Line and cable charging current under earth fault conditions

    A

    20

    12

    Rated short circuit breaking current

    kA

     

    31.5/50 (by the fuse may be)

    13

    Rated over current/transfer current

    A

    3150

    14

    Solid divided time

    ms

    45

    15

    Power frequency withstand voltage (1min)

    kV

    White, contrast, vacuum fracture: 42, isolated fracture between:48

    16

    Lightning impulse withstand voltage

    kV

    White, contrast, vacuum fracture: 75. isolated fracture between: 85

    17

    Mechanical life

    Times

    >10000

    Product Model

    Vacuum load isolation switch

    Vacuum load isolation switch.jpg

    Vacuum load isolation switch - fuse combinations

    Vacuum load isolation switch - fuse combinations.jpg

    Dimension

    2.jpg

    Product Functions

    ◆Load Current Switching: Safely makes and breaks load currents in 12kV three-phase AC systems.
    ◆Transformer Protection: Capable of breaking load transformers up to 2000kVA, protecting critical equipment.
    ◆Fault Current Handling: Rated overcurrent/transfer current of 3150A ensures reliable coordination with fuses for short-circuit protection.
    ◆Ground Fault Protection: Handles ground fault currents up to 20A, including line and cable charging currents under earth fault conditions.
    ◆High-Speed Operation: Over 10,000 mechanical life cycles guarantee long-term operational reliability.

    Applicable Environment

    ◇Rated System: Suitable for 12kV, 50Hz three-phase AC indoor power distribution systems.
    ◇Temperature Range: Reliable operation in ambient temperatures from -25℃ to +40℃.
    ◇Installation Altitude: Designed for installation at elevations up to 1000 meters.
    ◇Humidity Tolerance: Suitable for environments with daily average humidity ≤95% and monthly average ≤90%.
    ◇Seismic Resistance: Capable of withstanding earthquake intensity up to 8 degrees.
    ◇Air Quality: Requires environment free from corrosive gases, flammable substances, and significant pollution.

    Product Highlights

    ◆Superior Dielectric Strength: Dual-fracture design with vacuum (42kV/75kV) and isolating (48kV/85kV) ratings ensures excellent insulation.
    ◆Extended Mechanical Durability: Over 10,000 operations exceed standards for longer life and less maintenance.
    ◆High Fault Current Capacity: Withstands 25kA short-time current and 3150A overcurrent for robust fault protection.
    ◆Comprehensive Fault Handling: Rated for 20A ground fault and 20A charging current under earth fault conditions.
    ◆Industrial-Grade Protection: Handles demanding applications including transformer protection up to 2000kVA.
    ◆Dual-Function Integration: Combines load switching and visual isolation in one unit, saving space and ensuring safe disconnection.