High-Quality ZGS□-12 Combined Transformer from China Suppliers and Factory for Reliable Power Distribution
Product Model
Performance Parameters of Transformers
Performance Parameters of 10kV Prefabricated Substation S11, S13, S20 Series Oil-immersed Transformers
| Serial Number | Rated Capacity (kVA) | Rated Voltage - High Voltage (kV) | Rated Voltage - Low Voltage (kV) | Tapping Range (%) | Vector Group Symbol | No-load Current (%) - S9 | No-load Current (%) - S10/S11 | Loss (W) - No-load - S10 |
|---|---|---|---|---|---|---|---|---|
| 1 | 30 | 6 6.3 10 |
0.4 (0.69) |
±5 (±2×2.5) |
Yyn0 Dyn11 |
2.2 | 2.0 | - |
| 2 | 50 | 2.0 | 1.8 | - | ||||
| 3 | 63 | 1.9 | 1.5 | - | ||||
| 4 | 80 | 1.7 | 1.2 | - | ||||
| 5 | 100 | 1.6 | 1.1 | - | ||||
| 6 | 125 | 1.5 | 1.0 | 340 | ||||
| 7 | 160 | 1.4 | 1.0 | 400 | ||||
| 8 | 200 | 1.4 | 0.8 | 480 | ||||
| 9 | 250 | 1.2 | 0.8 | 560 | ||||
| 10 | 315 | 1.1 | 0.7 | 670 | ||||
| 11 | 400 | 1.0 | 0.7 | 800 | ||||
| 12 | 500 | 1.0 | 0.6 | 960 | ||||
| 13 | 630 | 0.9 | 0.6 | 1200 | ||||
| 14 | 800 | 0.8 | 0.6 | 1400 | ||||
| 15 | 1000 | 0.7 | 0.5 | 1700 | ||||
| 16 | 1250 | 0.6 | 0.5 | 1950 | ||||
| 17 | 1600 | 0.6 | 0.5 | 2400 |
| Serial Number | Loss (W) - No-load - S10 | Loss (W) - No-load - S11 | Loss (W) - Load - S9 | Loss (W) - Load - S10/S11 | Resistance Voltage (%) | Noise (dB) | Temperature Rise |
|---|---|---|---|---|---|---|---|
| 1 | 130 | - | 600 | 4 | 5.5 | Top oil Temperature 60° Coil 65° |
|
| 2 | 170 | - | 870 | ||||
| 3 | 200 | - | 1040 | ||||
| 4 | 250 | - | 1250 | ||||
| 5 | 290 | - | 1500 | ||||
| 6 | 270 | 1800 | |||||
| 7 | 310 | 2200 | |||||
| 8 | 375 | 2600 | |||||
| 9 | 455 | 400 | 3050 | 3000 | |||
| 10 | 540 | 475 | 3650 | 3600 | |||
| 11 | 650 | 570 | 4300 | 4200 | |||
| 12 | 775 | 680 | 5100 | 5000 | |||
| 13 | 920 | 800 | 6200 | 6000 | 4.5 | ||
| 14 | 1120 | 980 | 7500 | 7400 | |||
| 15 | 1320 | 1150 | 10300 | 9860 | |||
| 16 | 1560 | 1360 | 12800 | 12000 | |||
| 17 | 1880 | 1640 | 14500 | 14000 | |||
Note:
According to customer requirements, the high-voltage tap range of the transformer can be designed as ±2×2.5%.
According to customer requirements, the low-voltage of the transformer can be designed as 0.69kv.
Performance Parameters of Load Switch
| Rated Current (A) | Rated Voltage (kV) | Impulse Withstand Voltage (kV) | Power Frequency Withstand Voltage (1min.kV) | Rated Short-time Withstand Current (kA/s) | Short-circuit Making Current (kA) | Peak Withstand Current of Short-time Current (kA) | Number of Load Operations | Number of Mechanical Operations |
|---|---|---|---|---|---|---|---|---|
| 315 | 12 | 75 | 42 | 12.5/2 | 31.5 | 31.5 | 100 | 2000 |
| 630 | 12 | 75 | 42 | 16/4 | 40 | 40 | 100 | 3000 |
Dimensions
ZGS□ Standard Type Dimensions
| Standard Type | Capacity kVA | A | B | C | D | E | F | H |
|---|---|---|---|---|---|---|---|---|
| Standard Type | 100-250 | 1900 | 1650 | 1250 | 650/800 | 600 | 1410/1560 | 1450 |
| 315 | 1900 | 1650 | 1350 | 650/800 | 650 | 1460/1610 | 1450 | |
| 400-500 | 1900 | 1750 | 1450 | 650/800 | 650 | 1490/1640 | 1550 | |
| 630 | 1900 | 1750 | 1550 | 650/800 | 700 | 1580/1730 | 1550 | |
| 800 | 1900 | 1850 | 1550 | 650/800 | 700 | 1640/1790 | 1650 | |
| 1000 | 1900 | 1850 | 1650 | 650/800 | 700 | 1640/1790 | 1650 |
ZGS□ Enhanced Type Dimensions
| Standard Type | Capacity kVA | A | B | C | D | E | F | H |
|---|---|---|---|---|---|---|---|---|
| Standard Type | 100-250 | 2400 | 1650 | 1250 | 800 | 600 | 1560 | 1450 |
| 315 | 2400 | 1650 | 1350 | 800 | 650 | 1610 | 1450 | |
| 400-500 | 2400 | 1750 | 1450 | 800 | 650 | 1640 | 1550 | |
| 630 | 2400 | 1750 | 1550 | 800 | 700 | 1730 | 1550 | |
| 800 | 2400 | 1850 | 1550 | 800 | 700 | 1790 | 1650 | |
| 1000 | 2400 | 1850 | 1650 | 800 | 700 | 1790 | 1650 |
ZGS□ Enhanced Type Dimensions
| Standard Type | Capacity kVA | A | B | C | D | E | F | G | M | H |
|---|---|---|---|---|---|---|---|---|---|---|
| Standard Type | 100-250 | 2400 | 1750 | 1250 | 800 | 600 | 1750 | 1560 | 950 | 550 |
| 315 | 2400 | 1750 | 1350 | 800 | 650 | 1750 | 1610 | 950 | 550 | |
| 400-500 | 2400 | 1850 | 1450 | 800 | 650 | 1750 | 1640 | 950 | 550 | |
| 630 | 2400 | 1850 | 1550 | 800 | 650 | 1750 | 1720 | 950 | 550 | |
| 800 | 2400 | 1950 | 1650 | 800 | 650 | 1750 | 1790 | 950 | 550 | |
| 1000 | 2400 | 1950 | 1650 | 800 | 700 | 1750 | 1840 | 950 | 550 |
Frequently Asked Questions (FAQ)
What are the primary high-voltage and low-voltage ratings for the ZGS□-12 transformer series?
The standard high-voltage ratings support 6kV, 6.3kV, and 10kV configurations. The standard low-voltage rating is 0.4kV, with an optional 0.69kV configuration available upon custom request.
Can the high-voltage tapping range be customized?
Yes. While the standard tap range is ±5%, it can be custom-engineered to ±2×2.5% according to specific operational and customer requirements.
What are the allowable temperature rise limits during transformer operation?
The series operates within standard thermal thresholds: the allowable temperature rise is 60°C for the top oil layer and 65°C for the transformer coils.
What mechanical and electrical endurance ratings do the load switches provide?
Both 315A and 630A rated load switches deliver up to 100 on-load switching operations. The 315A switch provides 2,000 mechanical operations, while the 630A switch delivers up to 3,000 mechanical operations.
What is the difference between standard and enhanced dimension enclosures?
The standard type features a compact structure with an overall length (A) of 1900mm. The enhanced dimension models offer an expanded base length of 2400mm with modified depth and height parameters to provide additional compartment space and facilitate diverse installation requirements.
Which vector connection group symbols are available?
The combined transformer supports standard dual vector groups: Yyn0 and Dyn11.