High-Quality ZGS□-12 Combined Transformer
Product Model

Performance Parameters of Transformers
△Performance Parameters of 10kV Prefabricated Substation S11, S13, S20 Series Oil-immersed Transformers
|
Serial Number |
Rated Capacity(kVA) |
Rated Voltage-High Voltage(kV) |
Rated Voltage-Low Voltage(kV) |
Tapping Range(%) |
Vector Group Symbol |
No-load Current(%)-S9 |
No-load Current(%)-S10/S11 |
Loss(W)-No-load-S10 |
|
1 |
30 |
6 |
0.4 |
±5 |
Yyn0 |
2.2 |
2.0 |
|
|
2 |
50 |
2.0 |
1.8 |
|
||||
|
3 |
63 |
1.9 |
1.5 |
|
||||
|
4 |
80 |
1.7 |
1.2 |
|
||||
|
5 |
100 |
1.6 |
1.1 |
|
||||
|
6 |
125 |
1.5 |
1.0 |
340 |
||||
|
7 |
160 |
1.4 |
1.0 |
400 |
||||
|
8 |
200 |
1.4 |
0.8 |
480 |
||||
|
9 |
250 |
1.2 |
0.8 |
560 |
||||
|
10 |
315 |
1.1 |
0.7 |
670 |
||||
|
11 |
400 |
1.0 |
0.7 |
800 |
||||
|
12 |
500 |
1.0 |
0.6 |
960 |
||||
|
13 |
630 |
0.9 |
0.6 |
1200 |
||||
|
14 |
800 |
0.8 |
0.6 |
1400 |
||||
|
15 |
1000 |
0.7 |
0.5 |
1700 |
||||
|
16 |
1250 |
0.6 |
0.5 |
1950 |
||||
|
17 |
1600 |
0.6 |
0.5 |
2400 |
|
Serial Number |
Loss(W)-No-load-S10 |
Loss(W)-No-load-S11 |
Loss(W)-load-S9 |
Loss(W)-load-S10/S11 |
Resistance Voltage(%) |
Noise(dB) |
Temperature Rise |
|
1 |
130 |
|
600 |
4 |
5.5 |
Top oil Temperature 60° coil 65° |
|
|
2 |
170 |
|
870 |
||||
|
3 |
200 |
|
1040 |
||||
|
4 |
250 |
|
1250 |
||||
|
5 |
290 |
|
1500 |
||||
|
6 |
270 |
1800 |
|||||
|
7 |
310 |
2200 |
|||||
|
8 |
375 |
2600 |
|||||
|
9 |
455 |
400 |
3050 |
3000 |
|||
|
10 |
540 |
475 |
3650 |
3600 |
|||
|
11 |
650 |
570 |
4300 |
4200 |
|||
|
12 |
775 |
680 |
5100 |
5000 |
|||
|
13 |
920 |
800 |
6200 |
6000 |
4.5 |
||
|
14 |
1120 |
980 |
7500 |
7400 |
|||
|
15 |
1320 |
1150 |
10300 |
9860 |
|||
|
16 |
1560 |
1360 |
12800 |
12000 |
|||
|
17 |
1880 |
1640 |
14500 |
14000 |
|||
Note:
According to customer requirements, the high-voltage tap range of the transformer can be designed as ±2×2.5%.
According to customer requirements, the low-voltage of the transformer can be designed as 0.69kv.
△Performance Parameters of Load Switch
|
Rated Current(A) |
Rated Voltage(kV) |
Impulse Withstand Voltage(kV) |
Power Frequency Withstand Voltage(1min.kV) |
Rated Short-time Withstand Current(kA/s) |
Short-circuit Making Current(kA) |
Peak Withstand Current of Short-time Current(kA) |
Number of Load Operations |
Number of Mechanical Operations |
|
315 |
12 |
75 |
42 |
12.5/2 |
31.5 |
31.5 |
100 |
2000 |
|
630 |
12 |
75 |
42 |
16/4 |
40 |
40 |
100 |
3000 |
Dimensions
△ZGS□ standard type dimensions
|
Standard Type |
Capacity kVA |
A |
B |
C |
D |
E |
F |
H |
|
100-250 |
1900 |
1650 |
1250 |
650/800 |
600 |
1410/1560 |
1450 |
|
|
315 |
1900 |
1650 |
1350 |
650/800 |
650 |
1460/1610 |
1450 |
|
|
400-500 |
1900 |
1750 |
1450 |
650/800 |
650 |
1490/1640 |
1550 |
|
|
630 |
1900 |
1750 |
1550 |
650/800 |
700 |
1580/1730 |
1550 |
|
|
800 |
1900 |
1850 |
1550 |
650/800 |
700 |
1640/1790 |
1650 |
|
|
1000 |
1900 |
1850 |
1650 |
650/800 |
700 |
1640/1790 |
1650 |

△ZGS□ Enhanced Type Dimensions
|
Standard Type |
Capacity kVA |
A |
B |
C |
D |
E |
F |
H |
|
100-250 |
2400 |
1650 |
1250 |
800 |
600 |
1560 |
1450 |
|
|
315 |
2400 |
1650 |
1350 |
800 |
650 |
1610 |
1450 |
|
|
400-500 |
2400 |
1750 |
1450 |
800 |
650 |
1640 |
1550 |
|
|
630 |
2400 |
1750 |
1550 |
800 |
700 |
1730 |
1550 |
|
|
800 |
2400 |
1850 |
1550 |
800 |
700 |
1790 |
1650 |
|
|
1000 |
2400 |
1850 |
1650 |
800 |
700 |
1790 |
1650 |

△ZGS□ Enhanced Type Dimensions
|
Standard Type |
Capacity kVA |
A |
B |
C |
D |
E |
F |
G |
M |
H |
|
100-250 |
2400 |
1750 |
1250 |
800 |
600 |
1750 |
1560 |
950 |
550 |
|
|
315 |
2400 |
1750 |
1350 |
800 |
650 |
1750 |
1610 |
950 |
550 |
|
|
400-500 |
2400 |
1850 |
1450 |
800 |
650 |
1750 |
1640 |
950 |
550 |
|
|
630 |
2400 |
1850 |
1550 |
800 |
650 |
1750 |
1720 |
950 |
550 |
|
|
800 |
2400 |
1950 |
1650 |
800 |
650 |
1750 |
1790 |
950 |
550 |
|
|
1000 |
2400 |
1950 |
1650 |
800 |
700 |
1750 |
1840 |
950 |
550 |
Product Functions
◆Integrates high-voltage control, protection, substation, and distribution equipment.
◆Provides flexible power supply in ring-main, terminal, or dual-power modes.
◆Accommodates various low-voltage feeder requirements with customizable housing.
◆Offers transformer overload protection via high-voltage fuses housed in oil.
◆Allows for hot-plugging of 200A cable elbows with load operation.
Applicable Environment
◇Ambient Temperature: -30℃ to +40℃.
◇Altitude: ≤1000 meters.
◇Humidity: Average daily relative humidity ≤95%.
◇Installation Site: Minimal pollution, no corrosive/flammable gases, severe vibration, or inclinations >3°.
◇Other: Withstands specified wind speeds and seismic conditions.
Product Highlights
◆Compact & Space-Saving: Volume is approximately 1/3 to 1/2 of comparable European-style transformers.
◆Fully Sealed & Safe: Fully insulated structure requires no insulation distance, ensuring personnel safety.
◆High Reliability: Excellent transformer performance with low loss, noise, and strong overload/short-circuit resistance.
◆Flexible Configuration: Available in standard, enhanced, or comprehensive housing types for cost-effective selection.
◆Grid-Adaptive Design: Incorporates plug-in dry-type fuses tailored for Chinese grid requirements.