High Voltage Disconnect Switch GN30-12M Series | China Suppliers & Factory for 10kV AC Power Systems
Technical Specification
| Item | GN30-12M/400-12.5 | GN30-12M/630-20 | GN30-12M/1000-31.5 | GN30-12M/1250-31.5 | |
| GN30-12DM/400-12.5 | GN30-12DM/630-20 | GN30-12DM/1000-31.5 | GN30-12DM/1250-31.5 | ||
| Rated KVoltage(KV) | 2 | ||||
| Rated Current(A) | 400 | 630 | 1000 | 1250 | |
| Rated short-time withstand current(KA) | 12.5 | 20 | 31.5 | ||
| Rated short-circuit duration (S) | 4 | ||||
| Rated peak withstand current(KA) | 31.5 | 50 | 80 | ||
| Rated insulting level | Lightning impulse withstand voltage (KV) | Phase to phase/to earth:75、across open contacts:85 | |||
| 1 min.PF withstand voltage(KV) | Phase to phase/to earth:42、across open contacts:48 | ||||
Product Model
Dimension
Frequently Asked Questions (FAQ)
What are the available rated current options for the GN30-12 series?
According to the technical specifications, the GN30-12 series is available in four rated current options: 400A, 630A, 1000A, and 1250A.
What is the rated short-time withstand current for the GN30-12M/1250-31.5 model?
The rated short-time withstand current for the 1250A model is 31.5 KA with a rated short-circuit duration of 4 seconds.
What is the lightning impulse withstand voltage for the GN30-12 series?
The lightning impulse withstand voltage is 75 KV for phase-to-phase and to earth, and 85 KV across open contacts.
What is the 1 min power frequency (PF) withstand voltage of this equipment?
The 1-minute power frequency (PF) withstand voltage is 42 KV for phase-to-phase and to earth, and 48 KV across open contacts.
What is the rated peak withstand current for the GN30-12M/630-20 model?
The rated peak withstand current for the 630A model is 50 KA, whereas the 400A model is 31.5 KA, and the 1000A/1250A models are 80 KA.