HWX-12 Outdoor Ring Main Unit: China Suppliers & Factory for 12kV/24kV Gas-Insulated Switchgear
Product Model
Technical Parameters
Item Name |
Unit |
C-Load Switch Unit |
F-Combined Apparatus Unit |
V-Circuit Breaker Unit |
||
Data |
Data |
Data |
||||
Rated Voltage |
kV |
12/24 |
12/24 |
12/24 |
||
Rated Frequency |
Hz |
50 |
50 |
50 |
||
Rated Current |
A |
630 |
125 |
630 |
||
Rated Transfer Current |
A |
|
1750 |
|
||
Rated Insulation Horizontal |
1min Power Frequency Withstand Voltage (Phase to Ground) |
Phase-to-Phase, Phase-to-Ground |
kV |
|
42/65 |
|
Across the Break |
kV |
|
48/79 |
|
||
Lightning Impulse Withstand Voltage |
Phase-to-Phase, Phase-to-Ground |
kV |
|
75/125 |
|
|
Across the Break |
kV |
|
85/145 |
|
||
Rated Short-Circuit Breaking Current |
kV |
20 |
315 |
20 |
||
Rated Short-Circuit Making Current |
kA |
50 |
80 |
50 |
||
Rated Short-Circuit Making Current (Grounding Switch) |
kA |
50 |
|
50 |
||
Rated Short-Time Withstand Current |
Main Circuit |
kA |
20 |
20 |
20 |
|
Grounding Switch |
kA |
20 |
20 |
20 |
||
Rated Short-Time Duration |
Main Circuit |
S |
4 |
|
4 |
|
Grounding Switch |
S |
4 |
4 |
4 |
||
Rated Peak Withstand Current |
Main Circuit |
kA |
50 |
|
50 |
|
Grounding Switch |
kA |
50 |
50 |
50 |
||
Internal Arc Test (Internal Arcing Test) |
A |
630 |
20kA/0.5s |
630 |
||
Rated Closed-Loop Breaking Current |
A |
630 |
Restricted by Fuse |
630 |
||
Rated Active Load Breaking Current |
A |
10 |
Restricted by Fuse |
25 |
||
Rated Cable Charging Breaking Current |
Times |
5000 |
17.4 |
3000 |
||
Mechanical Life |
Load/Isolation Switch |
Times |
3000 |
5000 |
3000 |
|
Grounding Switch |
Times |
|
3000 |
10000 |
||
Vacuum Circuit Breaker |
Mpa |
|
|
|
||
SF6 Gas Pressure (Absolute Pressure at 20℃) |
|
|
0.035 |
|
||
Yearly Leakage Rate |
|
|
≤0.025% Year |
|
||
Cabinet and Fuse Protection Level |
|
|
IP67 |
|
||
Cabinet and Enclosure Protection Level |
|
|
IP41 |
|
||
Outdoor Ring Main Unit Protection Level |
|
|
IP44W |
|
||