Indoor Voltage Transformer (for Ring Network Cabinet)
Product Model

Technical Parameters
Take 10kV as reference
1. Rated insulation: horizontal 12/42/75kV
2. Power factor:cos Փ = 0.8 (lag)
|
Model |
Rated voltage ratio |
Accurate level and rated secondary output(VA) |
Limit output |
Remarks |
|
JSZW12A-10NFR |
|
3/3P |
3×500(1000) |
|
|
|
0.5/3/3P |
3×300/3×500(1000) |
220V For operation power supply |
|
|
0.5/3/3P |
||||
|
0.5/3/3P |
3×300/3×500(1000) |
Note: if there are special requirements for transformer ratio and load please indicate in the order.
Outline Dimension

Wiring Principle Diagram

Product Functions
◆Auxiliary Power Supply: Delivers a stable 220V power source for control and operational circuits within the switchgear.
◆System Voltage Measurement: Accurately measures the 10kV system voltage for monitoring, metering, and data collection.
◆Ground Fault Protection: Provides zero-sequence voltage signals essential for detecting single-phase ground faults and triggering protective relays.
◆Resonance Suppression: The core 4PT configuration actively prevents destructive ferromagnetic resonance in the PT system.
Applicable Environment
◇Primary Application: Installed inside enclosed Ring Main Units or indoor switchgear panels.
◇Electrical System: Rated for use in 10kV, 50Hz or 60Hz alternating current power distribution networks.
◇Setting: Designed exclusively for indoor environments, protecting against dust and condensation in electrical rooms or substations.
Product Highlights
◆State Grid Compliant: Manufactured according to State Grid standardization, ensuring compatibility and reliability in utility projects.
◆Advanced Anti-Resonance Design: The patented 4PT principle guarantees safe operation without resonance during ground faults, a critical safety feature.
◆Plug-and-Play Connection: Integrated with a standard American 200A elbow plug (with built-in fuse) for quick, secure, and safe primary circuit connection.
◆Robust Construction: Three phase five column iron-core design offers high measurement accuracy and durability for long service life.
◆Customization Available: Technical parameters can be tailored through negotiation with the manufacturer for special project needs.
Installation Instructions
◇Ensure the 10kV system is completely de-energized and grounded before starting any work.
◇Insert the elbow plug of the transformer firmly into the matching 200A bushing interface on the ring network cabinet until it clicks/locks securely.
◇Connect the secondary wiring (terminals a, n, da, dn) correctly to the corresponding measurement, protection, and power supply circuits as per the schematic diagram.
◇Verify the rating and integrity of the special fuse inside the elbow plug before energization.
◇After installation, perform necessary system tests (insulation resistance, ratio, polarity) and verify protection signal outputs before commissioning.