Indoor Voltage Transformer (for Ring Network Cabinet)

This JSZW12A-6、10NFR model is a State Grid-standardized, three-phase, five-column indoor voltage transformer designed for 10kV ring network cabinets. It employs a 4PT anti-ferromagnetic resonance design to prevent resonance during system ground faults, ensuring long-term, stable operation. Featuring a primary terminal with a fused American 200A large-diameter elbow plug, it provides 220V power supply, precise voltage measurement, and reliable zero-sequence protection in 50/60Hz AC systems.

    Product Model

    1.Indoor Voltage Transformer (For Ring Network Cabinet).jpg

    Technical Parameters

    Take 10kV as reference

    1. Rated insulation: horizontal 12/42/75kV

    2. Power factor:cos Փ = 0.8 (lag)

    Model

    Rated voltage ratio

    Accurate level and rated secondary output(VA)

    Limit output

    Remarks

    JSZW12A-10NFR

     

    3/3P
    3×500/100

    3×500(1000)

     

     

    0.5/3/3P
    3×30/3×300/30

    3×300/3×500(1000)

    220V For operation power supply

    0.5/3/3P
    3×30/3×300/50

    0.5/3/3P
    3×50/3×500/100

    3×300/3×500(1000)

    Note: if there are special requirements for transformer ratio and load please indicate in the order.

    Outline Dimension

    2.Indoor Voltage Transformer (For Ring Network Cabinet).jpg

    Wiring Principle Diagram

    3.Indoor Voltage Transformer (For Ring Network Cabinet).jpg

    Product Functions

    ◆Auxiliary Power Supply: Delivers a stable 220V power source for control and operational circuits within the switchgear.

    ◆System Voltage Measurement: Accurately measures the 10kV system voltage for monitoring, metering, and data collection.

    ◆Ground Fault Protection: Provides zero-sequence voltage signals essential for detecting single-phase ground faults and triggering protective relays.

    ◆Resonance Suppression: The core 4PT configuration actively prevents destructive ferromagnetic resonance in the PT system.

    Applicable Environment

    ◇Primary Application: Installed inside enclosed Ring Main Units or indoor switchgear panels.

    ◇Electrical System: Rated for use in 10kV, 50Hz or 60Hz alternating current power distribution networks.

    ◇Setting: Designed exclusively for indoor environments, protecting against dust and condensation in electrical rooms or substations.

    Product Highlights

    ◆State Grid Compliant: Manufactured according to State Grid standardization, ensuring compatibility and reliability in utility projects.

    ◆Advanced Anti-Resonance Design: The patented 4PT principle guarantees safe operation without resonance during ground faults, a critical safety feature.

    ◆Plug-and-Play Connection: Integrated with a standard American 200A elbow plug (with built-in fuse) for quick, secure, and safe primary circuit connection.

    ◆Robust Construction: Three phase five column iron-core design offers high measurement accuracy and durability for long service life.

    ◆Customization Available: Technical parameters can be tailored through negotiation with the manufacturer for special project needs.

    Installation Instructions

    ◇Ensure the 10kV system is completely de-energized and grounded before starting any work.

    ◇Insert the elbow plug of the transformer firmly into the matching 200A bushing interface on the ring network cabinet until it clicks/locks securely.

    ◇Connect the secondary wiring (terminals a, n, da, dn) correctly to the corresponding measurement, protection, and power supply circuits as per the schematic diagram.

    ◇Verify the rating and integrity of the special fuse inside the elbow plug before energization.

    ◇After installation, perform necessary system tests (insulation resistance, ratio, polarity) and verify protection signal outputs before commissioning.