Integrated Voltage and Current Combination Sensor
Product Model

Technical Parameters
Take the rated voltage of 10kV as reference
|
Parameter |
Value |
|
Rated voltage transformation ratio |
Three-phase sequence:10kV/√3/3.25V/√3 |
|
Rated current ratio |
Three-phase sequence:600A/1V |
|
Level of accuracy |
0.5/1;0.5S/5P10 |
|
Supply voltage |
single-phase:10kV/√3,DC27V,5W |
|
Insulation resistance |
>1000MΩ |
|
Rated load |
2MΩ |
|
Working frequency |
50(60)Hz |
|
Temperature range |
-40℃~70℃ |
|
Rated insulation level |
12/42/75kV |
Outline Dimension
Please install accessories such as arc extinguishing chamber, soft connection and guide rod according to the size of the pole. Refer to the output terminal layout drawing at the bottom of the pole for the installation holes of the box.

Install The Base

Product Functions
◆Simultaneously collects phase sequence, zero sequence, voltage, and current signals for comprehensive grid monitoring.
◆Integrates voltage and current sensors with energy-taking components directly within the circuit breaker pole.
◆Provides a stable auxiliary power output of 2-5W to support connected devices.
◆Offers customizable design to meet specific user requirements for transformation ratios, power parameters, and functionality.
Applicable Environment
◇Specifically engineered for State Grid primary-secondary integration intelligent circuit breaker bodies.
◇Ideal for smart grid applications requiring integrated sensing and power supply within compact circuit breaker installations.
◇Suitable for indoor electrical cabinets or breaker boxes where built-in, reliable signal acquisition and power output are needed.
Product Highlights
◆All-in-One Design: Voltage/current sensors and energy-taking components are fully built into the pole, saving space and simplifying installation.
◆Dual Capability: Combines precise electrical signal acquisition with useful power supply output (2-5W).
◆High Customizability: Can be tailored to user-defined voltage/current transformation ratios, power levels, and phase sequence requirements.
◆Grid-Optimized: Developed specifically for State Grid intelligent circuit breakers, ensuring compatibility and performance.
Installation Instructions
◇The sensor assembly is pre-integrated into the circuit breaker pole; ensure the pole is correctly installed in the breaker body.
◇The matching power supply device (energy-taking companion) must be installed inside the circuit breaker box as per design.
◇During ordering, provide the manufacturer with detailed specifications: rated voltage/current transformation ratios, single-pole supply voltage and power (2-5W range), and the designated power supply phase sequence.
◇For any special requirements, contact the manufacturer directly to arrange customization prior to installation.