Leave Your Message
pro_banner_013
JSZFW-6/10R Outdoor Anti-Resonance Voltage Transformer

JSZFW-6/10R Outdoor Anti-Resonance Voltage Transformer

The JSZFW-6/10R is a three-phase, five-column outdoor voltage transformer designed for reliability. It utilizes an anti-resonance winding configuration in a Y-type connection, effectively suppressing ferromagnetic resonance risks. The unit is constructed with a vacuum epoxy resin cast coil and sealed with durable silicone, ensuring excellent insulation and weatherproof performance. This robust design is suitable for accurate voltage transformation and measurement in demanding outdoor electrical environments.

    Product Model

    1.JSZFW-610R Outdoor Anti-Resonance Voltage Transformer.jpg

    Technical Parameters

    Take 10kV as reference

    1. Rated insulation:horizontal 12/42/75kV

    2. Power factor:cos Փ= 0.8 (lag)

    Model

    Rated voltage ratio

    Accurate level and rated secondary output(VA)

    Limit output

    Remarks

    JSZFW-10R

     

    3/3P
    3×500/100

    3×500(1000)

     

     

    0.5/3/3P
    3×30/3×300/30

    3×300/3×500(1000)

    220V For operation power supply

    0.5/3/3P
    3×30/3×300/50

    0.5/3/3P
    3×50/3×500/100

    3×300/3×500(1000)

    Note: if there are special requirements for transformer ratio and load, please indicate in the order.

    Outline Dimension

    2.JSZFW-610R Outdoor Anti-Resonance Voltage Transformer.jpg

    Wiring Principle Diagram

    3.JSZFW-610R Outdoor Anti-Resonance Voltage Transformer.jpg

    Product Functions

    ◆Voltage Transformation: Steps down high primary system voltage to standardized, safe secondary levels for metering and protection equipment.

    ◆System Monitoring: Provides precise voltage signals for system monitoring, energy metering, and data acquisition.

    ◆Resonance Suppression: Its specific winding design prevents damaging ferromagnetic resonance, which can occur during system disturbances like single-pole switching.

    ◆Insulation & Grounding: The anti-resonance winding provides a dedicated path for zero-sequence currents, enhancing system stability during unbalanced conditions.

    Applicable Environment

    ◇Location: Designed for installation in outdoor substations, switchyards, or along power distribution lines.

    ◇Climate: Built to withstand harsh environmental conditions, including rain, humidity, UV exposure, and wide temperature fluctuations.

    ◇Electrical System: Rated for use in 6kV or 10kV, 50/60Hz three-phase AC power distribution networks.

    Product Highlights

    ◆Advanced Anti-Resonance Design: Unique three-phase, five-column core and specialized winding structure guarantee protection against system ferromagnetic resonance.

    ◆Robust Outdoor Construction: Vacuum-cast epoxy resin provides exceptional dielectric strength and mechanical protection for the coils, while silicone sealing ensures long-term waterproof and dustproof integrity.

    ◆High Reliability: The solid insulation system and durable materials offer a maintenance-free design with a long operational lifespan under outdoor conditions.

    ◆Accurate Performance: Delivers high-precision voltage transformation for reliable measurement and control signals.

    ◆Customizable: The JSZFW model can be tailored to specific technical parameters based on project requirements.

    Installation Instructions

    ◇Safety First: Ensure the primary high-voltage circuit is de-energized, isolated, and grounded according to all local safety regulations before beginning installation.

    ◇Foundation & Mounting: Securely mount the transformer on a stable, level base or structure suitable for its weight and dimensions, as per the dimensional drawing.

    ◇Electrical Connections: Connect the primary terminals to overhead lines or busbars. Terminate secondary windings to measurement, protection, and metering panels, ensuring correct phase sequence and anti-resonance winding grounding.

    ◇Grounding: Establish a reliable and low-resistance connection from the transformer's designated grounding point to the station's main grounding grid.

    ◇Pre-commissioning Check: Before energization, perform a visual inspection, verify all electrical connections and grounding, and conduct recommended insulation resistance tests.