KYN28A-12 Metal Enclosed Switchgear - High-Quality China Suppliers & Factory for 3.6-12kV Distribution Solutions
📦 Product Model
⚙️ Technical Parameters
| Parameter | Value |
|---|---|
Rated Voltage (kV) |
3/6/10 |
Maximum Operating Voltage (kV) |
3.6/7.2/12 |
Power Frequency Withstand Voltage (kV) |
42 (1min) |
Impulse Withstand Voltage (kV) |
75 |
Rated Frequency |
50Hz |
Rated Current (A) |
630–3150 |
Rated Thermal Stability Current (kA/4s) |
16–50 |
Rated Dynamic Stability Current (kA) |
40–125 |
Rated Short-Circuit Breaking Current (kA) |
16–50 |
Rated Short-Circuit Making Current (kA) |
40–125 |
Rated DC Voltage for Opening/Closing Switch and Auxiliary Circuits |
24, 30, 48, 60, 110, 220, AC 110, 220 |
Protection Class |
IP4X |
| Items | Unit | VSI | VD4 | |||
|---|---|---|---|---|---|---|
Rated Voltage |
kV |
3.6 |
6 |
10 |
||
Maximum Operating Voltage |
kV |
3 |
7.2 |
12 |
||
Rated Insulation Level |
Power Frequency Withstand Voltage for 1 minute |
kV |
42 |
|||
Lightning Impulse Withstand Voltage |
kV |
75 |
||||
Rated Frequency |
Hz |
50 |
||||
Rated Current |
A |
630, 1250, 1600, 2000, 2500, 3150 |
||||
Rated Short-Circuit Breaking Current (RMS) |
kA |
16, 20, 25, 31.5, 40, 50 |
||||
4S Thermal Stability Current (RMS) |
kA |
16, 20, 25, 31.5, 40, 50 |
||||
Rated Dynamic Stability Current (Peak) |
kA |
40, 50, 63, 80, 100, 125 |
||||
Transient Recovery Voltage Rate |
kV/ms |
0.345 |
0.415 |
|||
Peak Transient Recovery Voltage |
kV |
20.6 |
30 |
|||
Rated Operation Sequence |
|
Split - 0.3 seconds - Merge - 180 seconds - Merge |
||||
Automatic Reclosing Operation Sequence |
|
Split - 0.3 seconds - Merge split - 3 minutes - Merge split |
||||
Multiple Reclosing Operation Sequence |
|
Split - 0.3 seconds - Merge - 15 seconds - Merge - 15 seconds - Merge |
||||
Closing Time |
ms |
100 |
70 |
|||
Opening Time |
ms |
20 |
45 |
|||
Arcing Time |
ms |
15 |
15 |
|||
Breaking Time |
ms |
65 |
60 |
|||
🔧 The Schematic Diagram of the Switchgear Structure
- A. Busbar Compartment
- B. Circuit Breaker Trolley Compartment
- C. Cable Compartment
- D. Relay and Instrument Compartment
- 1.1 Pressure Relief Device
- 1.2 Control Cable Tray
- 1. Enclosure
- 2. Branch Busbar
- 3. Busbar Sleeve
- 4. Main Busbar
- 5. Static Contact Device
- 6. Static Contact Box
- 7. Current Transformer
- 8. Grounding Switch
- 9. Cable
- 10. Surge Arrester
- 11. Grounding Main Busbar
- 12. Removable Partition
- 13. Partition (Live Door)
- 14. Secondary Plug
- 15. Circuit Breaker Trolley
- 16. Heating Device
- 17. Withdrawable Horizontal Partition
- 18. Grounding Switch Operating Mechanism
- 19. Base Plate
📐 The Outline Dimensions of the Switchgear
** Cable Inlet and Outlet Dimensions: 1500mm for Overhead Lines and 1660mm for Overhead Lines
🏗️ Switchgear Base Installation Diagram
| Cabinet Width | Cabinet Depth | M | N | L |
|---|---|---|---|---|
800 |
1500 Cable |
630 |
800 |
1450 |
1660 Overhead |
1610 |
|||
1000 |
1500 Cable |
830 |
1000 |
1450 |
1660 Overhead |
1610 |
📏 Switchgear Installation Dimension Diagram
| Cabinet Width | Cabinet Depth | L1 | L2 | L3 |
|---|---|---|---|---|
800 |
1500 Cable |
530 |
630 |
800 |
1660 Overhead |
||||
1000 |
1500 Cable |
730 |
830 |
1040 |
1660 Overhead |
📏 Switchgear Installation Dimension Diagram
| Cabinet Depth | L |
|---|---|
1500 |
1450 |
1660 |
1610 |