MNS Low-Voltage Withdrawable Switchgear
Technical Parameters
(1)Electrical Performance
|
Rated Insulation Voltage |
600V |
|
Rated Operating Voltage |
380V,660V |
|
Maximum Operating Current of Main Busbar |
5000A |
|
Rated Withstand Current of Main Busbar |
100kA |
|
Rated Peak Withstand Current of Main Busbar |
220kA |
|
Maximum Operating Current of Distribution Busbar(VerticaBusbar) |
1000A |
|
Peak Current of Distribution Busbar(Vertical Busbar) |
80kA |
|
Standard Type |
105kA(max) |
|
Enhanced Type |
176kA(max) |
(2) Protection Class
Compliant with IEC 529, DIN 40050 standards
IP30 protection against solid objects greater than Փ2.5mm
IP40 protection against solid objects greater than Փ1.5mm
IP54 protection against dust and splashing from any direction
(When ordering IP54 protection level, it should be negotiated with the manufacturer)
Cabinet Structure
The basic structure of the switchgear cabinet is assembled from C-shaped profiles. The C-shaped profiles are made of steel plates bent with a modulus of E=25mm for mounting holes. All the cabinet frames and inner partitions are galvanized for purification. The surrounding door panels and side panels are coated with high-voltage electrostatic spray. The basic structure of the cabinet is shown in Figure 1, and the basic dimensions of the cabinet are shown in Tables 1 and 2.

Product Functions
This switchgear is designed for power generation, transmission, distribution, energy conversion, and control of consumption equipment in three-phase five-wire systems (400V, 660V, up to 5000A). It provides centralized power management and protection for applications in utilities, industry, and commercial buildings. Additionally, it supports reactive power compensation for the main busbar via capacitor compensation cabinets, improving overall system efficiency and power quality.
Applicable Environment
It operates reliably in ambient temperatures from -5°C to +40°C (24h average ≤ +35°C), at altitudes up to 2000m, and in clean air with controlled humidity (≤50% at +40°C, up to 90% at +20°C). The unit withstands transportation/storage from -25°C to +55°C, with short-term exposure up to +70°C (≤24h) without irreversible damage. For non-standard conditions or specialized installations (e.g., offshore platforms, nuclear plants), a separate technical agreement is required.
Product Highlights
◆Safe Operation: Equipped with secure mechanical interlocking devices on drawers, ensuring user safety and preventing operational errors.
◆Modular Flexibility: Constructed from standardized, serialized modules, allowing for customizable configurations, easy maintenance, and scalability.
◆Wide Compliance: Manufactured in accordance with GB 7251.1 and IEC 60439 standards, ensuring international quality and safety benchmarks.
◆Robust Design: Engineered to perform under specified environmental and temperature extremes, guaranteeing durability and consistent performance.