YB□ High Voltage/Low Voltage Prefabricated Substation from China Suppliers - Factory Integrated Power Distribution Solutions
Product Model
Main Technical Parameters
| Name | Unit | High-voltage Electrical Equipment | Transformer | Low-voltage Electrical Equipment |
|---|---|---|---|---|
| Rated Voltage | kV | 10 | 10/0.4 | 0.4 |
| Rated Current | A | 630 | 100~2500 | |
| Rated Frequency | Hz | 50 | 50 | 50 |
| Rated Capacity | kVA | 100~1250 | ||
| Rated Thermal Stability Current | kA | 20/4S | 30/1S | |
| Rated Dynamic Stability Current (Peak) | kA | 50 | 63 | |
| Rated Closing Short-circuit Current (Peak) | kA | 50 | 15~30 | |
| Rated Breaking Short-circuit Current | kA | 31.5 (Fuse) | ||
| Rated Breaking Load Current | А | 630 | ||
| 1min Power Frequency Withstand Voltage | kV | Phase-to-ground, Phase-to-phase 42, and Across-the-isolator 48 | 35/28 (5min) | 2.0/2.5 |
| Lightning Impulse Withstand Voltage | kV | Phase-to-ground, Phase-to-phase 75, and Across-the-isolator 85 | 75 | |
| Enclosure Protection Level | IP23 | IP23 | IP23 | |
| Noise Level | dB | Oil-immersed ≤55 Dry-type Transformer ≤65 |
||
| Number of Circuits | piece | 1~6 | 2 | 4~30 |
| Maximum Reactive Power Compensation on Low Voltage Side | kvar | 300 |
The Layout Form and External Dimensions
Frequently Asked Questions (FAQ)
-
QWhat is the rated voltage range of the YB High Voltage/Low Voltage Prefabricated Substation?The high-voltage side operates at 10 kV, while the transformer steps it down to 10/0.4 kV, and the low-voltage side operates at 0.4 kV, making it suitable for standard medium-voltage distribution networks.
-
QWhat transformer capacity options are available for this prefabricated substation?The transformer rated capacity ranges from 100 kVA to 1,250 kVA, supporting both oil-immersed and dry-type transformer configurations to meet various application requirements.
-
QWhat is the enclosure protection level of the YB Prefabricated Substation?All three sections — high-voltage equipment, transformer, and low-voltage equipment — are protected to IP23 standard, providing protection against solid objects larger than 12.5mm and against water spray at an angle up to 60° from vertical.
-
QHow many output circuits does the low-voltage side support?The low-voltage electrical equipment supports between 4 and 30 output circuits, offering flexible configuration for various distribution needs in commercial, industrial, and residential projects.
-
QDoes the YB Prefabricated Substation support reactive power compensation?Yes. The low-voltage side supports a maximum reactive power compensation of up to 300 kvar, helping to improve power factor and reduce energy losses in the distribution system.
-
QWhat are the lightning impulse withstand voltage ratings for the high-voltage section?The high-voltage equipment is rated at 75 kV for phase-to-ground and phase-to-phase lightning impulse withstand voltage, and 85 kV across the isolator, ensuring reliable performance during transient overvoltage events.