ZW32-24 Series 24kV Outdoor High Voltage Vacuum Circuit Breaker - China Suppliers & Factory
⚙️ Technical Specification
| No. | Item | Units | Parameters | ||
| 1 | Rated voltage | kV | 24 | ||
| 2 | Rated frequency | Hz | 50 | ||
| 3 | Rated current | A | 630 | 1250 | |
| 4 | Rated short-circuit breaking current | kA | 20 | 25 | |
| 5 | Rated peak withstand current (peak) | KA | 50 | 63 | |
| 6 | Rated short-circuit closing current (peak) | kA | 50 | 63 | |
| 7 | Rated short-time withstand current and duration | kA/s | 20/4 | 25/4 | |
| 8 | Rated operation sequence | O-0.3s-CO-180s-CO | |||
| 9 | Mechanical life | Times | 10000 | ||
| 10 | Breaking times of rated short-circuit breaking current | Times | 20 | ||
| 11 | 1min power frequency withstand voltage | (wet) over the ground / interphase / fracture | kV | 50/65 | |
| (dry) over the ground / interphase / fracture | 65/79 | ||||
| Secondary loop | 2 | ||||
| 12 | Lighting impulse withstand voltage (peak) Over the ground, interphase / fracture | kA | 125/145 | ||
| 13 | Weight | kg | 115 | ||
📐 Product Model
📏 Dimension
❓ Frequently Asked Questions
Q
What is the rated voltage of this vacuum circuit breaker?
The rated voltage of this vacuum circuit breaker is 24 kV, making it suitable for medium-voltage power distribution systems.
Q
What rated current options are available for this breaker?
This vacuum circuit breaker is available in two rated current options: 630 A and 1250 A, providing flexibility for different load requirements.
Q
What is the mechanical life expectancy of this circuit breaker?
The mechanical life of this vacuum circuit breaker is rated at 10,000 operating cycles, ensuring long-term reliability and reduced maintenance costs.
Q
What is the rated short-circuit breaking current capacity?
The rated short-circuit breaking current is available in 20 kA and 25 kA options, with a rated short-time withstand duration of 4 seconds, ensuring safe operation under fault conditions.
Q
What is the standard operating sequence for this breaker?
The rated operation sequence is O-0.3s-CO-180s-CO, which complies with standard IEC requirements for medium-voltage vacuum circuit breakers.
Q
What are the power frequency withstand voltage levels for this breaker?
Under wet conditions, the 1-minute power frequency withstand voltage is 50 kV (over ground/interphase) and 65 kV (fracture). Under dry conditions, it is 65 kV (over ground/interphase) and 79 kV (fracture). The secondary loop withstand voltage is 2 kV.