ZW7-40.5 Outdoor Vacuum Circuit Breaker - Reliable 40.5kV High Voltage Solutions from China Suppliers & Factory
No. |
Item |
Units |
Parameters |
||
1 |
Rated voltage |
KV |
40.5 |
||
2 |
Rated insulation level |
Power frequency withstand voltage |
Dry |
95 |
|
Wet |
80 |
||||
Lightning impulse withstand voltage (peak) |
|
185 |
|||
3 |
Rated current |
A |
1250、1600、2000 |
||
4 |
Rated short-circuit breaking current |
KA |
20、25、31.5 |
||
5 |
Rated operating sequence |
|
O-0.3s-CO-180s-CO |
||
6 |
Rated short-circuit breaking current breaking times |
Times |
12 |
||
7 |
Rated short-circuit closed current (peak) |
KA |
50、63、80 |
||
8 |
Rated peak withstand current |
||||
9 |
Rated short-time withstand current |
KA |
20、25、31.5 |
||
10 |
Rated short-circuit duration |
S |
4 |
||
11 |
Average opening speed |
m/s |
1.5±0.2 |
||
12 |
Average closing speed |
0.7±0.2 |
|||
13 |
Contact closing bounce duration |
s |
≤2 |
||
14 |
Three phase closing and opening synchronism |
≤2 |
|||
15 |
Opening time |
≤150 |
|||
16 |
Closing time |
≤60 |
|||
17 |
Mechanism life |
Times |
10000 |
||
18 |
Rated operating voltage and auxiliary circuit rated voltage |
V |
Dc220、110、24 |
||
Ac220、110、24 |
|||||
19 |
Phase loop DC resistance (without current transformer) |
uΩ |
≤100 |
||
20 |
Permitted accumulate wear-thickness of dynamic and static contact |
mm |
3 |
||
21 |
Weight |
kg |
800 |
||